Error code: d3

Cause of error code d3

Temperature high limit defective.
External guard has tripped.
Temperature limiter locked out.

Solution for error code d3

Check temperature sensor and leads for interruptions or shorts, and replace if defective.
Temperature guard TB1 has tripped. Check if jumper across8-9 or PR-P0 is missing.
Reset external temperature limiter (if installed).
Reset LWCO (if installed).