Error code:

105
List all errors


Error code: 105

Cause of error code 105

Flame detected out of sequence 

Solution for error code 105

-Check that flame is not present in the combustion chamber. Correct any errors.
-Make sure that the flame detector is wired to the correct terminal.
-Make sure the F & G wires are protected from stray noise pickup.
-Reset and sequence the module, if code reappears, replace the flame detector.
-Reset and sequence the module, if code reappears, replace the module.