ErrorHelp.us

Heating  Heating

Brand

Bradford White Bradford White List all brands

Type:

brute Mini BJVS-225 view brute Mini BJVS-225 List all types

Error code:

105
List all errors


Error code: 105

Cause of error code 105

Flame detected out of sequence 

Solution for error code 105

-Check that flame is not present in the combustion chamber. Correct any errors.
-Make sure that the flame detector is wired to the correct terminal.
-Make sure the F & G wires are protected from stray noise pickup.
-Reset and sequence the module. If code reappears, replace the flame detector.
-Reset and sequence the module.  If code reappears, replace the module.


 

Share this page: Facebook Twitter





© 2025 ErrorHelp.us