Ignit Error
- Three unsuccessful ignition attempts in a row
- If the gas supply pressure is incorrect, it must be adjusted to the correct pressure.
- If spark is not present check for correct ignition electrode position.
- If the combustion air pressure is incorrect, inspect the vent system and eliminate any obstructions.
- If the voltage to the gas valve is not 120Vac the power control board must be replaced.