Error code: 15

Cause of error code 15

Return temp higher than supply

The Control is reading a return sensor temperature higher than the supply sensor temperature. Condition must be present for at least 75 seconds for this error code to appear.

Solution for error code 15

• Flow through boiler reversed. Verify correct piping and circulator orientation.
• No boiler water flow. Verify that system is purged of air and that appropriate valves are open.
• Sensor wiring reversed.
• Supply or return sensor defective.