Error code: E39

Cause of error code E39

Flue temperature sensor sees temperature higher than 200°F.

Solution for error code E39

1. Read flue gas temperature on User Interface. Is temperature higher than 200°F? 
Yes: Boiler is over fired. Wait for boiler to cool. Fix flow rate problem if any, purging all air out of the system.
No: -> 2


2. Use thermal couple to measure flue gas temperature through sampling port. Is the measured temperature and flue temperature reading on User Interface significantly different? 
Yes: Replace Flue Gas Sensor
No: Replace Control Module