Boiler power supply ground wire is not grounded.
1. Is field grounding conductor connected to High Voltage Terminal Strip 120 VAC (G)?
Yes: -> 2
No: Connect ground conductor
2. Disconnect field wiring. Is continuity between field wiring neutral and ground less than 10 ohms?
Yes: Replace Control Module
No: Correct faulty ground conductor