Flue temperature sensor is open. No continuity.
1. Is harness plugged into vent temperature sensor? Is harness plugged into control module J5?
Yes: -> 2
No: Insert harness
2. Disconnect harness from vent temperature senor and control module J5. Continuity for each blue wire?
Yes: -> 3
No: Replace wire
3. Measure resistance across vent temperature sensor terminal. Does resistance match estimate flue temperature?
Yes: Replace control module
No: Replace vent temperature senor.