Supply temperature sensor is open. No continuity.
1. Is harness plugged into Supply Water Sensor? Is harness plugged into Control Module J5?
Yes: -> 2
No: Insert Harness
2. Disconnect J5 from control module. Using digital meter measure check continuity of white wires between control board and sensor. Continuity?
Yes: -> 3
No: Replace wires
3. Unplug J5 connector on comtrol board. Using digital meter measure resistance between terminals J5-11 and J5-3. Estimate sensor temperature. Does it fall in the range of the resistance chart?
Yes: Repalce control module.
No: Replace supply water sensor.