Casting temperature switch opened.
1. Determine reason for limit action and correct. Check for air trapped at top of casting.
2. If limits are closed, check wiring and connections. Apply a temporary jumper across terminals 6 and 8 and check operation. If problem persists, check boiler internal wiring. Replace low voltage harness if necessary. Replace control module if harness replacement doesn’t resolve.