ErrorHelp.us

Heating  Heating

Brand

HTP HTP List all brands

Type:

Elite EL-220 view Elite EL-220 List all types

Error code:

F02
List all errors


Error code: F02

Cause of error code F02

F02 indicates the supply temperature sensor of the boiler has failed. The boiler will not restart until a technician replaces the sensor and pushes RESET on the display. This is a serious safety issue as indicated by the illuminated red light and the word LOCKOUT flashing on the display. During this lockout fault, the pump will be on. 

Solution for error code F02

- Check the electrical connection to the thermistor on the outlet manifold. Verify 5 VDC by checking the Molex connector. If there is no 5 VDC, check the harness. If harness is OK, replace the control. Verify thermistor values by referencing chart in this manual.
- Replace thermistor if necessary. NOTE: The boiler will reset automatically once the fault is corrected.


Share this page: Facebook Twitter