ErrorHelp.us

Heating  Heating

Brand

HTP HTP List all brands

Type:

Enduro TI ETI-750 view Enduro TI ETI-750 List all types

Error code:

E07
List all errors


Error code: E07

Cause of error code E07

This display indicates that the flue sensor temperature is above 210ºF. When this code is displayed, the boiler will not respond to a demand for heat. When the flue temperature decreases below 194ºF, the display will return to normal and allow the boiler to respond to a heat demand. The bottom line indicates the status of the pump. The pump will remain on when this error is displayed.

Solution for error code E07

Check the flue for obstructions or any sign of damage, especially signs of excessive heat. Repair as necessary. Run the boiler and check the flue temperature with an external thermometer. If the flue temperature on the thermometer does not agree with the flue temperature displayed in the status menu, inspect the wiring to the flue temperature sensor in the boiler and repair as necessary. If the wiring is intact, replace the flue sensor. If the flue temperature is excessive on the status menu and the test thermometer reads the same, check and adjust combustion controls on the boiler. 


Share this page: Facebook Twitter





© 2025 ErrorHelp.us