Error code: F05

Cause of error code F05

F05 indicates the boiler supply temperature


is excessive. When accompanied by the


red FAULT light and LOCKOUT flashing on


the display, this code indicates the supply


sensor temperature has exceeded 230oF and


a serious safety issue exists. The boiler will


not restart until a technician determines and


repairs the cause of excessive temperature


and pushes RESET on the display.


If the FAULT light is not illuminated and


this message is displayed, the supply


temperature of the boiler is at or above


210oF. The message will clear automatically


when the temperature drops below 194oF.


During the time that this fault is displayed,


the pump will be on.

Solution for error code F05

- Check circulator pump operation.


- Ensure adequate flow through the boiler by accessing the status menu and determining there is less than a 50°F rise from the return thermistor to the supply thermistor.


- Check the direction of flow off the boiler circulator.


- Troubleshoot the dual supply thermistor by following steps in F02.