ErrorHelp.us

Heating  Heating

Brand

HTP HTP List all brands

Type:

Enduro TI ETI-750 view Enduro TI ETI-750 List all types

Error code:

F09
List all errors


Error code: F09

Cause of error code F09

The boiler tried to ignite four times during one heat call and failed. This is a serious safety issue as indicated by the illuminated red light and the word LOCKOUT flashing on the display. The boiler will not restart until a technician determines and repairs the cause of ignition failure and pushes RESET on the display. During this lockout fault, the pump will remain on.

Solution for error code F09

- Watch the igniter through the observation window.
- If there is no spark, check the spark electrode for the proper 1/4” gap between the burner.
- Remove any corrosion from the spark electrode.
- If there is a spark but no flame, check the gas supply to the boiler.
- If there is a flame, check the flame current.
- Check any flue blockage or condensate blocks.
-  Replace the ignitor. 


Share this page: Facebook Twitter





© 2025 ErrorHelp.us