Error code: F10

Cause of error code F10

The flame was lost while the boiler was firing 3 times during 1 demand call. The red light will display and the word LOCKOUT will flash. This code indicates a serious safety issue. The boiler will not restart until the cause of flame loss is determined by a technician and he pushes the RESET button on the display. During this lockout fault, the pump will be on as indicated on the second line of the display.

Solution for error code F10

- Monitor the gas pressure to the boiler while in operation.


- Assure that the flame is stable when lit.


- Check to see if the display readout changes from “GAS VALVE ON” to “RUN” within a few seconds after the boiler ignites.


- Check the FLAME signal on the status display. It should be above 1.0 when the boiler is firing.


- If the signal reads less than 1 microampere, clean the flame rectifier and spark probe.


- If the problem persists and the ‘FLAME” signal is still less than 1.0, replace the flame probe and spark igniter probe.


- The flame signal should be steady after the boiler has been firing for 1 minute and is normally at 5.0 to 9.0. If the flame signal is not steady, disassemble the burner door and check the burner and its sealing gaskets.