ErrorHelp.us

Heating  Heating

Brand

HTP HTP List all brands

Type:

Mod Con 500 After december 2012 view Mod Con 500 After december 2012 List all types

Error code:

F00
List all errors


Error code: F00

Cause of error code F00

This display indicates if the water in the boiler has overheated. This code indicates a serious safety issue and the boiler will not restart until it cools sufficiently and a technician repairs the cause of overheating and pushes the RESET button on the display. This is a serious situation and is indicated by the red light on the display illuminating and the word LOCKOUT flashing on the display. During this lockout fault, the pump will be on as indicated on the second line in an effort to cool the boiler down.

Solution for error code F00

- Check circulator pump operation


- If the circulator pump is running, be sure that there is water in the system and that the water is moving through the system as intended. Be sure that all correct ball valves and or zone valves are open or closed as intended.


- Observe the temperature/pressure gauge. If the water is not too hot and this message is displayed, check the wiring to the water ECO sensor and repair if necessary. If the wiring is ok and this code is still present and the water is not excessively hot, replace the ECO sensor.


Share this page: Facebook Twitter





© 2025 ErrorHelp.us