Error code: F10

Cause of error code F10

Loss of flame signal – The heater will relight 4 times before the control goes into this lockout condition. Will reset in 1 hour.

Solution for error code F10

- Monitor the gas pressure to the unit while in operation.
- Assure that the flame is stable when lit.
- Check to see if the green light on the display module is out while the heater is running. |
- If the green light doesn’t come on or goes off during operation check the flame signal on the status menu.
- If the signal reads less than 1 microampere, clean the flame rectifier probe. - If the flame rectifier probe continues to read low, replace it.