ILK (Interlock) ON
- Check wiring and correct any possible shorts.
- Check Interlock (ILK) switches to assure proper function.
- Verify voltage through the interlock string to the interlock input with a voltmeter.
- If steps 1-3 are correct and the fault persists, replace the module.