ErrorHelp.us

Heating  Heating

Brand

Laars Laars List all brands

Type:

Magnatherm MGV4000 view Magnatherm MGV4000 List all types

Error code:

156
List all errors


Error code: 156

Cause of error code 156

Combustion pressure and flame ON

Solution for error code 156

- Check that flame is not present in the combustion chamber. Correct any errors.
- Make sure that the flame detector is wired to the correct terminal.
- Make sure the F & G wires are protected from stray noise pickup.
- Reset and sequence the module, if code reappears, replace the flame detector.
- Reset and sequence the module, if code reappears, replace the module.


Share this page: Facebook Twitter