Flue sens open.
1. Is harness plugged into Vent Temperature Sensor? Is harness plugged into Control Module J5?
Yes: -> 2.
No: Insert harness
2. Disconnect harness from Vent Temperature Sensor and Control Module J5. Continuity for each blue wire?
Yes: ->3.
No: Replace wires.
3. Measure resistance across Vent Temperature Sensor terminals. Does resistance match estimated flue temperature?
Yes: Replace Control Module.
No: Replace Vent Temperature Sensor.