3 flame failures.
1. Inspect harness connection Flame Sensor. Is connection clean and secure?
Yes: -> 2.
No: Replace Flame Sensor or harness.
2. Remove Flame Sensor. Is rod free of contamination?
Yes: -> 3
No: Clean or replace Flame Sensor.
3. Follow OPERATING INSTRUCTIONS to initiate boiler operation. Enter Installer Menu, Boiler Status, Flame Signal. Is flame signal greater than 3.7 uA?
Yes: Replace Control Module.
No: Replace Flame Sensor and Burner.