Error code: High Outlet Water Temp

Cause of error code High Outlet Water Temp

1 Modulating valve is not in AUTO Mode


2 Modulating valve lost calibration


3 Heat exchanger scaled on DHW side

Solution for error code High Outlet Water Temp

1 - Rotate valve handle until it is in AUTO Mode


2 - Remove cover on modulating valve electronics and press the recessed calibration button to re-calibrate the valve


3 - Clean and de-scale heat exchanger.