Error code: Flow switch/LWCO

Cause of error code Flow switch/LWCO

1. Either the optional flow switch or the optional low water cutoff is not making.
2. Blown fuse.

Solution for error code Flow switch/LWCO

1. - Check boiler pump operation on a call for heat. 
- Check for closed valves or obstructions in the boiler piping. 
- Verify system is full of water and all air has been purged from the system. 
- Check for loose or misplaced jumpers if flow switch or LWCO is not installed on the Low Voltage Connection Board.


2. Replace fuse F3 on the control board.