Error code:

Delta T high
List all errors


Error code: Delta T high

Cause of error code Delta T high

The temperature rise across the heat exchanger has exceeded the set parameters for the boiler.

Solution for error code Delta T high

- Verify that the system is full of water and that all air has been properly purged from the system. 
- Verify that the boiler is piped properly into the heating system. 
- Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. 
- If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. 
- Verify that the boiler pump is set to the proper speed or that the pump is the proper size. 