Error code: Service blk

Cause of error code Service blk

While the unit is in Service Mode, the outlet temperature has exceeded 185°F.

Solution for error code Service blk

- Establish a heating load to remove the heat from the boiler loop. 
- Verify that the system is full of water and that all air has been properly purged from the system. 
- Verify that the boiler is piped properly into the heating system. 
- Check 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. 
- If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. 
- Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size.