Error code: Outlet MRHL

Cause of error code Outlet MRHL

The outlet water temperature has exceeded the setting of the manual reset high limit.

Solution for error code Outlet MRHL

- Adjust the set point of the manual reset limit to a higher setting up to a maximum of 210°F. Reference the Knight Boiler Installation and Operation Manual for adjusting procedures.
- Verify that the system is full of water and that all air has been properly purged from the system.  
- Verify that the boiler is piped properly into the heating system.
- Replace the main control board if necessary.
- If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.
- If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow.
- If operating on something other than an outlet sensor, check temperature setting of the main control board.
- If the optional manual reset high limit has tripped, check setting of the device.
- Check resistance of water sensors. Replace sensor if necessary. 
- Replace high limit.