ErrorHelp.us

Heating  Heating

Brand

Lochinvar Lochinvar List all brands

Type:

WBN051 view WBN051 List all types

Error code:

Outlet MRHL
List all errors


Error code: Outlet MRHL

Cause of error code Outlet MRHL

The outlet water temperature has exceeded the setting of the manual reset high limit.

Solution for error code Outlet MRHL

- Adjust the set point of the manual reset limit to a higher setting up to a maximum of 210°F.


- Verify that the system is full of water and that all air has been properly purged from the system.


- Verify that the boiler is piped properly into the heating system.


- Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board.


- If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.


- If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow.


- If operating on something other than an outlet sensor, check temperature setting of the main control board.


- Check resistance of water sensors. Replace sensor if necessary.


- Replace the main control board if necessary.


Share this page: Facebook Twitter





© 2025 ErrorHelp.us