APS open
List all errors


Error code: APS open

Cause of error code APS open

Air pressure switch contacts are open.

Solution for error code APS open

- Check the wiring connections to switch. Wires should be connected to the common and normally closed terminals. 


- Air intake lengths exceed the maximum allowed lengths. 


- Check for obstruction or blockage in the air intake pipes or at terminations. 


- Check reference hoses connected to the air pressure switch for blockage or obstruction.


- Inspect the burner. Replace if necessary. 


- Inspect the heat exchanger. Replace if necessary.


- Faulty air pressure switch. Replace switch.