Error code: Flame fail running

Cause of error code Flame fail running

The unit was running and lost the flame signal. This condition occurred five (5) straight times during the same call for heat.

Solution for error code Flame fail running

- Check wiring harness connection at the gas valve and at the main control board.


- Inspect spark electrode and associated wiring for damage and connection.


- Check incoming supply gas pressure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c.


- Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged.


- Verify that the vent/air intake pipes are correctly installed and that there are no obstructions.


- Check for 24 vac to the gas valve at the 2-pin connection on the side of the main control board during the ignition attempt. If no voltage is present, replace the main control board.


- If 24 vac is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary.


- If 24 vac is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve.


- Inspect and clean the heat exchanger as necessary.