Error code: Outlet ARHL

Cause of error code Outlet ARHL

The outlet water temperature has exceeded the setting of the automatic reset high limit.

Solution for error code Outlet ARHL

- Adjust the set point of the auto reset limit to a higher setting up to a maximum of 200°F.


- Verify that the system is full of water and that all air has been properly purged from the system.


- Verify that the boiler is piped properly into the heating system.


- Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board.


- If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.


- If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow.


- If operating on something other than an outlet sensor, check temperature setting of the main control board.


- Check resistance of water sensors. Replace sensor if necessary.


- Replace the main control board if necessary.