Error code: Flame fail Ing

Cause of error code Flame fail Ing

The unit has failed to prove main burner ignition after four (4) attempts.

Solution for error code Flame fail Ing

- Check wiring harness connection at the gas valve and at the main control board.


- Inspect spark electrode and associated wiring for damage and connection.


- Check for proper electrical grounding of the unit.


- Check incoming supply gas pressure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c.


- Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged.


- Verify that the vent/air intake pipes are correctly installed and that there are no obstructions.


- Check for 24 vac to the gas valve at the 2-pin connection on the side of the main control board during the ignition attempt. If no voltage is present, replace the main control board. 


- If 24 vac is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary.


- If 24 vac is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve.


- Inspect flame sensor and associated wiring. Replace if necessary.


- Inspect the burner. Replace if necessary. 


- Replace the main control board.