ErrorHelp.us

Heating  Heating

Brand

NTI Boilers NTI Boilers List all brands

Type:

Trinity Fire Tube (Tft110) view Trinity Fire Tube (Tft110) List all types

Error code:

Lockout 82
List all errors


Error code: Lockout 82

Cause of error code Lockout 82

1. Dirty heat exchanger
2. Incorrect “Stack limit setpoint”
3. Faulty sensor

Solution for error code Lockout 82

1. Inspect and if required clean the combustion chamber and/or heat exchanger.
2. Unless installed in Canada with PVC exhaust venting, set “Stack limit setpoint” to maximum setting of 220ºF (104ºC). In Canada PVC exhaust venting is limited to 149ºF (65ºC).
3. Check resistance of sensor and compare to thermistor resistance chart,


Share this page: Facebook Twitter