ErrorHelp.us

Heating  Heating

Brand

NTI Boilers NTI Boilers List all brands

Type:

Trinity Fire Tube (Tft60) view Trinity Fire Tube (Tft60) List all types

Error code:

Lockout 122
List all errors


Error code: Lockout 122

Cause of error code Lockout 122

1. Blower is not turning on.
2. Missing or incorrect blower feedback signal.
3. Blower is always on. 

Solution for error code Lockout 122

1. - Check Demand and Setpoints via Touchscreen. Check thermostat and DHW aquastat settings (as applicable). 
- Check Demand and Setpoints via Touchscreen. Check thermostat and DHW aquastat settings (as applicable).
- Check outlet temperature, setpoint and hysteresis settings via Touchscreen.
- Check Summary page on Touchscreen for code.
- Check Summary page, if Demand indicates “Burner switch off” go to diagnostics burner test page and switch on.
2. See errorcode Hold 62 
3. - Verify that the 5-position Molex connector on the wiring harness is securely connected to its mating connector on the blower.
- Check that the 4-position Molex connector on wiring harness is securely connected to its mating connector on the Sola controller.
- Check Power LED on Sola controller.
- Check Fuse "C".
- With an AC voltmeter measure voltage at terminals J8 1 & 2, 24VAC should be present.


Share this page: Facebook Twitter