ErrorHelp.us

Heating  Heating

Brand

NTI Boilers NTI Boilers List all brands

Type:

Trinity TX101 view Trinity TX101 List all types

Error code:

Err 65
List all errors


Error code: Err 65

Cause of error code Err 65

Incorrect Polarity

Solution for error code Err 65

Controller has sensed reversed polarity of the 120VAC power supply; check field wiring to L2 NEUTRAL (terminals 12 &13) and L1 120VAC (terminal 14). There should be 120VAC potential between L1 120VAC and ground, and 0VAC potential between L2 NEUTRAL and ground.