ErrorHelp.us

Heating  Heating

Brand

NTI Boilers NTI Boilers List all brands

Type:

Trinity TX200 view Trinity TX200 List all types

Error code:

Err 66
List all errors


Error code: Err 66

Cause of error code Err 66

Incorrect Frequency

Solution for error code Err 66

The controller accepts a line voltage frequency of 60Hz ± 2%; if outside this range the controller may be damaged or function incorrectly. If using a generator as a power source, install a UPS (uninterruptible power supply) between the generator and boiler.