Cause of error code Loc 31

Flame lost three times during one demand

Solution for error code Loc 31

1. Check venting for blockages. 
2. Check condensate trap from proper draining.
3. Static gas pressure – if insufficient check gas supply-lines and regulator.
4. Gas pressure during ignition – if the static gas pressure is sufficient, check pressure during ignition sequence, i.e. when gas valve opens. 
a. If pressure drops below minimum (4” for NG / 8” for LP), check gas supply-line and regulator. 
b. If pressure does not move, verify 120VDC at valve during ignition; if no power, check wiring – replace control; if power is present – replace gas valve.
c. If pressure drops slightly – proceed to next step
5. Unit ignites but immediately goes out – check flame sensor (clean or replace) and flame sensor cable, clean combustion chamber, replace control. If a combustion analyzer is available, adjust throttle screw out 1 turn – check/adjust combustion once unit is operational. 
6. Unit fails to ignite – check spark electrode and cable (replace). Verify the spark electrode is arcing. WARNING!! – maintain clearance from ignition components while the power is on to avoid risk of severe electrical shock. 
7. Unit ignites and runs – check combustion at maximum and minimum modulation rates.