U1 or U6 sensor increase its temperature too fast.
1. Check that the heating water flow is not too low. If temperature difference between U1 and U8 is higher than 55°F (13°C), at maximum input, the heating water flow rate is too low. The heating water flow rate must be corrected.
2. Check that the circulator pump is working. If the pump works, replace the power control board.