ErrorHelp.us

Heating  Heating

Brand

Peerless Peerless List all brands

Type:

PureFire PF-110 view PureFire PF-110 List all types

Error code:

A03
List all errors


Error code: A03

Cause of error code A03

Overheat limit open


High Temperature Limit Open (Set Temperature 205°F)

Solution for error code A03

- Check CH, DHW, General Pump Operation
- Assure that there is adequate flow through the boiler by checking the status menu and assuring less than 40°F temperature rise across the boiler.      
- Check thermistor reading on the supply thermistor. Replace it if necessary.


Share this page: Facebook Twitter