Overheat limit open
High Temperature Limit Open (Set Temperature 205°F)
- Check CH, DHW, General Pump Operation
- Assure that there is adequate flow through the boiler by checking the status menu and assuring less than 40°F temperature rise across the boiler.
- Check thermistor reading on the supply thermistor. Replace it if necessary.