Supply sensor not connected.
- Supply sensor circuit is open.
- Be sure sensor is plugged in.
- Check continuity in both harness leads.
- Temporarily connect the harness to another sensor to determine if the error is cleared. If so, this indicates a defective sensor.
- Read the sensor temperature values in the “User Menu” under “Status”. 14°F indicates an open circuit.
Note: The component with the red connector is the high limit switch not a sensor.