ErrorHelp.us

Heating  Heating

Brand

Peerless Peerless List all brands

Type:

PureFire PF-850 view PureFire PF-850 List all types

Error code:

A02
List all errors


Error code: A02

Cause of error code A02

Flame failure.


- Flame failures have exceeded the maximum allowed.

Solution for error code A02

- Check the burner flame signal at high and low fire. If it is less than 5.0 μA, clean the flame sensor. If the problem persists, change the sensor.
- If the flame signal is above 5.0 μA, check for possible wind gusts while the boiler is on low fire. If there is indication of this issue, increase the minimum fan speed to prevent further occurances. 


Share this page: Facebook Twitter