High Temperature Limit Open [Set Temperature: 195°F (90.5°C)]
1. Check pump operation.
2. Assure that there is adequate flow through the boiler by checking the status menu and assuring less than 40°F (4.4°C) temperature rise across the boiler.
3. Check thermistor reading on the supply thermistor. Replace it if necessary.