Error code: E02

Cause of error code E02

No ?ame formation 


1. No temperature difference between supply (3) and return (4)


2. There is a temperature difference between supply (3) and return (4)

Solution for error code E02

Check the data in Error mode. Boiler data during error.
1 error  = 02
2 operational status  =  02
3 supply temp.  =  xx*
4 return temp.  =  xx*
5 kW burner  =  xx**
6 % pump  =  xx*
* = variable value
**= x 3451 = BTU/hr


1.Boiler has not been able to ignite any gas or has not received any gas. Boilertries to start 6 times with an increasing starting load after the safety time. 
Check whether:
- the gas valve is open;
- there is power to the gas valve;
- that the gas valve opens
The minimum gas pre-pressure during the start must be a minimum of 7"W.C.(17 mbar), check the 24 Volts in the gas during ignition block’s open position.


2. Boiler has gone out  after ignition. Due to insuf? cient ionization the burner has gone out after ignition.
Ionization ?ow, ionization cable or the O2 setting. The minimum ionization current should be 4 μA, the O2 should be a minimum of 4.4% for NG or 4.8% for LP