Error code: Lockout 122

Cause of error code Lockout 122

Light off rate proving failed.


1. Blower is not turning on. 
2. Missing or incorrect blower feedback signal 
3. Blower is always on. 
4. Incorrect Sola controller.


 

Solution for error code Lockout 122

1.  - Blower power disconnected; Verify that the 3-position Molex connector on the wiring harness is securely connected to its mating connector on the blower.
- Blown fuse; Check Fuse "A" using the procedure described above. Fuse "A" protects the blower as well as the ignition spark generator and appliance pump. 
- Faulty blower; Measure voltage across pins 1 & 2 (black and white wires) of 3-position connector on wiring harness. If 120VAC detected, replace power connector and remove 5-position signal connector. Blower should rotate at high speed. If blower does not rotate, replace blower. 
2. Check error code "Hold 62"
3. - Blower signal cable disconnected; Verify that the 5-position Molex connector on the wiring harness is securely connected to its mating connector on the blower. Check that the 4-position Molex connector on wiring harness is securely connected to its mating connector on the Sola controller. 
- No 24VAC to Sola controller; Check Power LED on Sola controller. Check Fuse "C". With an AC voltmeter measure voltage at terminals J8 1 & 2, 24VAC should be present. 
4. Replace control with correct model.


 