Error code: A02

Cause of error code A02

Flame Failure - 3 losses of flame signal during one demand.

Solution for error code A02

Check for proper combustion, at both max. and min. input firing rates. If combustion is within the range, clean or replace spark ignitor, check power supply voltage and grounding.