Error code: 29

Cause of error code 29

APS/Condensate – Closed is Normal, Open is Fault (Condensate Drain Trap) 

Solution for error code 29

Press the Power button to clear the Error Code.
1. Check APS/Condensate and main controller connections. Ensure all are secure. 2. Check APS/Condensate resistance. If resistance is zero, replace the switch.
3. Check APS/Condensate hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check exhaust vent for blockages. 6. If the problem persists, replace the main control