Error code: Err4

Cause of error code Err4

Burner Output (B1) Fault


 

Solution for error code Err4

B1 output sensed powered during safety output relay check sequence or unpowered during running, or powered in idle in combination with water temperature above 264°F limit. Cycle power to the control. Replace control if problem persists.