ErrorHelp.us

Heating  Heating

Brand

U.S.Boiler Company U.S.Boiler Company List all brands

Type:

MPO-IQ189 view MPO-IQ189 List all types

Error code:

ErP4
List all errors


Error code: ErP4

Cause of error code ErP4

Warning, Cad Cell Resistance High (service required)

Solution for error code ErP4

The cad cell resistance is higher than normal while running, the system is in need of a tune up.
-Check for proper alignment of the cad cell and clean the eye if necessary.
-Check if the pump is generating adequate pressure.
-Check burner adjustments (refer to burner manufacturers instructions).
-Check for excessive soot build up in the burner and flue.
-Check for flue blockage.


Share this page: Facebook Twitter





© 2025 ErrorHelp.us