Retry / Recycle Delay
The Boiler is in “Retry Delay”:
-The burner failed to light (no flame signal). After a 5 minute delay, control will attempt to light the burner again. There is no limit to the number of retries.
Recycle Delay
-The burner loses flame during running mode, “STA 8”. After a 10 second delay, control will attempt to light the burner again. If the burner loses flame during running mode, “STA 8” during the next six recycles, control will progress to a soft lockout.