Cause of error code Err56

Damper Failed to Close


 

Solution for error code Err56

Damper open. Voltage should not be present on P6-5.  Control, vent damper or wire harness is defective.  While the Err 56 is displayed by the control, perform the following tasks:
-Remove the call for heat (adjust thermostat or remove wire from TT     terminals.
-Check for 24Vac between P6-5 and ground.
-If voltage not present, attempt to start boiler again.
-If 24Vac is present, unplug the vent damper harness from  control.
-With wire harness unplugged, check for 24Vac between P6-5 (on Control)   and ground.
-If voltage present, replace the control.
-If voltage not present, failed vent damper or wiring harness.
-Check wiring harness for shorts or mis-wiring.  Replace if defective.
-If harness not defective, replace vent damper.